Thermal Comfort and Air Change Rate Study for a Naturally Ventilated Classroom: A Case Study of El-Baida City, Libya
Abstract
Nowadays in buildings and environments, it is of a functional requirement to fulfill a robust design by diminishing the energy consumption while keeping the environmental factors surrounding the individuals within a comfort range. Natural ventilation in buildings is considered an advantageous attempt to serve those purposes. In Libya, most of the educational buildings are utilizing the natural ventilation systems where the energy consumption is minimized while the internal temperatures and humidity are constrained, indoor air is replenished, and all other contaminants are reduced. Although extensive overseas research has been carried out in this regard, few studies have touched the thermal comfort and internal environmental attributes influencing the performance of students in Libya. The main objective of this study was to investigate qualitatively and quantitatively the thermal comfort and air change rate of a naturally ventilated classroom located in El-Baida City, Libya. The thermal comfort of one classroom was evaluated by calculating the values of the Predicted Mean Vote (PMV) and Predicted Percentage Dissatisfied (PPD) indices. This was accomplished by measuring the six main indoor parameters of thermal comfort, namely, air temperature, Mean Radiant Temperature (MRT), relative humidity, air velocity, activity level, and clothing insulation. Also, (PMV) and (PPD) were calculated in parallel to ASHRAE 55-2010 and ISO 7730 by using MATLAB. Additionally, a field survey was completed by distributing comfort questionnaires to estimate Thermal Sensation Votes (TSV), which were then compared with computed (PMV) and (PPD). The results highlighted that while computed values of (PMV) and (PPD) for the classroom were thermally satisfactory according to ASHRAE standard 55 and ISO 7730, the Thermal Sensation Vote (TSV) based on the questionnaire showed that the classroom did not satisfy the thermal criteria in ASHRAE.
Full text article
References
[1]-T. A. M. .Hamad, "Study of thermal comfort applications in schools of Libya," Master degree, Department of Mechanical and Industrial Engineering, Tripoli, Libya, 2007.
[2]-R. Daghigh, N. M. Adam, B. Sahari, and B. A. Yousef, "Thermal comfort study and ventilation evaluation of an office," Advances in Mechanical Engineering and its Application, vol. 3, pp. 278-83, 2012.
[3]-S. Haddad, S. King, and P. Osmond, "Enhancing thermal comfort in school buildings," in Proceedings of the 10th International Healthy Building Conference, Brisbane, Australia, 2012, pp. 8-12.
[4]-Ç. Çakir, "Assessing thermal comfort conditions: a case study on the METU Faculty of Architecture building," Middle East Technical University, 2006.
[5]-T. L. Madsen and T. L. Madsen, Thermal environmental parameters and their measurement: Technical University of Denmark, 1976.
[6]-R. De Dear, K. Leow, and S. Foo, "Thermal comfort in the humid tropics: Field experiments in air conditioned and naturally ventilated buildings in Singapore," International Journal of Biometeorology, vol. 34, pp. 259-265, 1991.
[7]-A. G. Kwok, "Thermal comfortin naturally-ventilated and air-conditioned classrooms in the tropics," 1997.
[8]-C. Huizenga, S. Abbaszadeh, L. Zagreus, and E. A. Arens, "Air quality and thermal comfort in office buildings: results of a large indoor environmental quality survey," 2006.
[9]-D. Mumovic, M. Davies, C. Pearson, G. Pilmoor, I. Ridley, H. Altamirano-Medina, et al., "A comparative analysis of the indoor air quality and thermal comfort in schools with natural, hybrid and mechanical ventilation strategies," Proceedings of Clima WellBeing Indoors, vol. 23, 2007.
[10]-S. MAAROF, "THERMAL COMFORT FACTORS IN HOT AND HUMID REGION: MALAYSIA."
[11]-T. A. Longo, A. P. Melo, and E. Ghisi, "Thermal comfort analysis of a naturally ventilated building," in Proceedings of Building Simulation 12th Conference ofInternational Building Performance Simulation Association, Sydney, 2011, pp. 2004-2010.
[12]-N. Muhamad Salleh, S. N. Kamaruzzaman, R. Sulaiman, and N. S. Mahbob, "Indoor air quality at school: Ventilation rates and it impacts towards children: A review," 2011.
[13]-U. Ioana, C. Cristiana, N. Ilinca, D. Angel, and B. Viorel, "Thermal Comfort Analyses in Naturally Ventilated Buildings," Mathematical Modelling in Civil Engineering, vol. 10, pp. 60-66, 2014.
[14]-Y. Hou, J. Liu, and J. Li, "Investigation of indoor air quality in primary school classrooms," Procedia Engineering, vol. 121, pp. 830-837, 2015.
[15]-L. D. Pereira, L. Neto, and M. G. Da Silva, "Indoor air quality and thermal comfort assessment of two Portuguese secondary schools: main results," in Proceedings of REHVA Annual Conference" Advanced HVAC and Natural Gas Technologies", 2015, pp. 49-56.
[16]-S. Vilčeková, P. Kapalo, Ľ. Mečiarová, E. K. Burdová, and V. Imreczeová, "Investigation of Indoor Environment Quality in Classroom-Case Study," Procedia engineering, vol. 190, pp. 496-503, 2017.
[17]-A. Ranjbar, "Analysing the effects of thermal comfort and indoor air quality in design studios and classrooms on student performance," in IOP Conference Series: Materials Science and Engineering, 2019, p. 042086.
[18]-Y. LI, Y. GAO, J. WANG, and E. LONG, "ASSESSMENT ON INDOOR THERMAL ENVIRONMENT OF RESIDENTIAL BUILDING ROOM WITH CAPILLARY-TUBE AIR CONDITIONING SYSTEM."
[19]-E. Iso, "7730: 2005," Ergonomics of the thermal environment-Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria, 2005.
[20]-S. Haddad, "Thermal Comfort in Naturally Ventilated Schools-A field study of thermal comfort in Iranian primary school classrooms," 2016.
[21]-M. Benedettelli, B. Naticchia, A. Carbonari, and M. Pascucci, "Testing of a Tracer Gas Based Measurement Procedureto Assess Air Change Rates in Buildings," in ISARC. Proceedings of the International Symposium on Automation and Robotics in Construction, 2015, p. 1.
[22]-A. ASTM, "E741-11: Standard Test Method for Determining Air Change in a Single Zone by Means of a TracerGas Dilution," ASTM Standard, 2011.
[23]-S. Cui, M. Cohen, P. Stabat, and D. Marchio, "CO2 tracer gas concentration decay method for measuring air change rate," Building and environment, vol. 84, pp. 162-169, 2015.
Authors

This work is licensed under a Creative Commons Attribution 4.0 International License.
In a brief statement, the rights relate to the publication and distribution of research published in the journal of the University of Sebha where authors who have published their articles in the journal of the university of Sebha should how they can use or distribute their articles. They reserve all their rights to the published works, such as (but not limited to) the following rights:
- Copyright and other property rights related to the article, such as patent rights.
- Research published in the journal of the University of Sebha and used in its future works, including lectures and books, the right to reproduce articles for their own purposes, and the right to self-archive their articles.
- The right to enter a separate article, or for a non-exclusive distribution of their article with an acknowledgment of its initial publication in the journal of Sebha University.
Privacy Statement The names and e-mail addresses entered on the Sabha University Journal site will be used for the aforementioned purposes only and for which they were used.